Tri-fuel

A tri-fuel generator runs on gasoline, propane, or natural gas. The natural-gas option lets a portable unit draw unlimited fuel from the home’s gas meter — with the lowest output of the three fuels, typically about 20% below the gasoline rating.

Natural gas has the lowest energy density of the three fuels, hence the deeper derating; propane sits between at roughly 10% below gasoline. In exchange, a natural-gas quick-connect on the house line ends fuel logistics entirely for long outages.

The natural-gas hookup requires a plumber or gas fitter to install a properly sized quick-connect tee, and the meter must have capacity for the generator on top of the furnace and water heater.

Output on natural gas Roughly 20–30% below the gasoline rating; propane sits about 10% below
Natural gas energy ≈1,030 BTU/ft³; 100 ft³ ≈ 1 therm (100,000 BTU)
Supply pressure Generators typically specify 7–11 in WC static and no less than about 5 in WC while running — residential service is around 7 in WC
Meter capacity Common residential meters pass 250–425 ft³/hr in total; a 22 kW standby alone needs about 300 ft³/hr at full load
Gas piping Sized per NFPA 54 (National Fuel Gas Code); a long run to a generator often needs 1 in or 1¼ in pipe
Hookup cost Roughly $500–$2,000 for a short run, more if the meter has to be upsized

The derating, fuel by fuel, and why it happens

The order is always gasoline, then propane, then natural gas, and the reason is the energy density of the intake charge. Natural gas is mostly methane arriving at near-atmospheric pressure, so it displaces a large fraction of the air the engine could otherwise breathe; propane displaces less; gasoline, injected or metered as a liquid that vaporises in the port, displaces least. Typical published numbers on a tri-fuel portable: 9,500 W on gasoline, about 8,500 W on propane, and about 7,000–7,600 W on natural gas. Manufacturers publish all three columns on tri-fuel units, and the natural-gas column is the one to use if the house line is the primary plan.

The surge rating derates by the same proportion, and surge is what starts motors. A tri-fuel unit that starts a one-horsepower well pump on gasoline may simply refuse to on natural gas. If a well pump is the reason the generator exists, size from the natural-gas surge figure, fit a soft starter, or accept that pump duty means switching to gasoline or propane.

What you buy with that lost 20–30% is the only fuel that does not run out. Buried gas distribution usually survives the storms that take down overhead power lines, so a tri-fuel portable connected to the house line behaves like a standby generator you can also wheel away. The failure cases are real but narrow: earthquakes trigger automatic and utility shutoffs, and a main break or an extreme cold snap can interrupt supply. Keeping the gasoline and propane paths is the entire point of buying tri-fuel rather than a natural-gas-only unit.

The gas connection: pressure, meter capacity, and pipe size

Residential gas leaves the meter regulator at about seven inches of water column — roughly a quarter of a pound per square inch, which is far lower than most people assume. Generator manuals typically want 7–11 in WC static and no less than about 5 in WC with the engine at full load. Pressure drop along an undersized run is what ruins these installations: the generator starts, runs well, and then falls on its face the moment the furnace also fires and the shared pipe cannot supply both.

Meter capacity is the next constraint and it is pure arithmetic. At about 1,030 BTU per cubic foot, a 22 kW air-cooled standby needs roughly 300 ft³/hr at full load and about 190 at half; a 7,500–9,500 W tri-fuel portable needs roughly 100–150 ft³/hr. Now add the existing house: a 100,000 BTU/hr furnace is 97 ft³/hr, a 40,000 BTU/hr water heater is 39, a range is around 65, a dryer around 22. A common 250 ft³/hr meter has no room left for a generator. Utilities will usually swap a meter for a larger one at little or no cost — but on their schedule, which is not during a storm.

Piping is sized from NFPA 54, the National Fuel Gas Code, using tables that combine run length, allowable pressure drop, and total demand. A sixty-foot run out to a generator pad commonly lands on 1 in or 1¼ in black iron where the ½ in branch that fed a barbecue would have been fine. Every installation needs an accessible manual shutoff valve and a sediment trap at the appliance, and the flexible connection must be a listed connector rather than a barbecue hose. This is gas-fitter work under its own permit, entirely separate from the electrical permit for the inlet and transfer equipment.

Quick-connects, hose length, and the 20-foot problem

The usual arrangement is a tee off the house line, a hard-piped run to an exterior wall or a pad, and a listed quick-disconnect fitting at the end. You wheel the generator out, snap the hose on, open the valve, and start. Connectors and hoses for portable outdoor gas appliances fall under ANSI Z21.54; length is limited, commonly to about twelve to fifteen feet, and joining two hoses to gain reach is specifically not permitted.

That creates a direct conflict with generator placement. CPSC wants a running generator at least twenty feet from the house with the exhaust pointed away, and a twelve- to fifteen-foot hose does not reach twenty feet from the wall the stub comes out of. The correct resolution is a longer hard-piped run terminating where the generator will actually stand, not a longer hose. Decide where the generator lives before the pipe is installed, because moving a stub afterwards means opening a trench.

Running cost is where natural gas justifies itself. At $1.20 per therm, a portable drawing 120 ft³/hr costs about $1.50 an hour to run. The same machine on gasoline at 0.9 gal/hr and $3.50 a gallon costs $3.15 an hour, and on exchange-cylinder propane closer to $5. Over a four-day outage running twenty hours a day, that is roughly $120 against $250 against $400 — and no queuing at a gas station that has no power to run its pumps.

Conversion kits and the legal position

Aftermarket kits that add natural gas to a gasoline or dual-fuel generator are widely sold and mostly work. They are also a modification of a certified engine’s fuel system, which the Clean Air Act treats as tampering unless the kit carries its own EPA certification for that engine family — and a CARB Executive Order if the machine is in California. Many are marketed with language about off-road or emergency use that does not create an exemption, and engine manufacturers routinely deny warranty claims on units carrying them. A factory tri-fuel generator is certified as built.

Whichever route you take, budget for two trades and two permits — a gas fitter for the tee, pipe, shutoff valve, sediment trap, and quick-connect, and an electrician for the inlet, cord, and transfer equipment. Both are inspected, and pricing them together avoids discovering the second job after the first is finished.

Frequently asked questions

How much power does a generator lose on natural gas?

Roughly 20–30% compared with its gasoline rating, on both running and starting watts. A 9,500 W gasoline portable typically produces about 7,000–7,600 W on natural gas, and about 8,500 W on propane. Tri-fuel spec sheets publish all three figures; size your load list against the natural-gas column if the house line is your primary supply.

Can I connect a portable generator to my house natural gas line?

Yes, with a tri-fuel or natural-gas-capable generator and a properly installed connection: a licensed gas fitter tees off the house line, runs correctly sized pipe to where the generator will stand, and terminates in a listed quick-disconnect with an accessible shutoff valve and a sediment trap. What you must not do is feed it from a barbecue hose and regulator — the pressure and flow are wrong, and the connector is not listed for the application.

Do I need a bigger gas meter for a generator?

Often yes, and it is easy to check. Add up your existing appliances in BTU per hour — a typical furnace is 80,000–120,000, a water heater around 40,000, a range around 65,000 — divide by 1,030 to get cubic feet per hour, then add the generator’s figure. A 22 kW standby needs about 300 ft³/hr on its own. If the total exceeds the meter’s rating, usually printed on the meter itself, the utility has to upsize it. Ask early: it is normally cheap but not fast.

What gas pressure does a natural gas generator need?

Most specify 7–11 inches of water column at the inlet with the engine off, and require it not to fall below about 5 in WC at full load. Standard residential service downstream of the meter regulator is around 7 in WC, which is adequate provided the pipe run is sized correctly. Where a house is fed at 2 psi with appliance regulators, the generator gets its own regulator.

Is tri-fuel worth it over dual-fuel?

Only if you have natural gas service and will actually pay for the hookup — usually $500–$2,000, sometimes with a meter upgrade on top. Where that is true, tri-fuel converts a portable into something close to an unlimited-runtime standby unit at a fraction of the price. Where there is no gas service, the third fuel is a badge on the box, and a dual-fuel unit at a lower price does the same job.

← All glossary terms